Step 2: Design of an assembly and design verification Rated current of an outgoing circuit (I nC ) First, the installation device of the outgoing circuits is selected based on the electrical function, e.g. fuses, circuit breakers, switch disconnectors, etc. Then the short list is based on the rated current of the circuits (I nc ). The rated current of the circuit (I nc ) must not exceed 80% of the rated current of the installed device, IEC 61439-1 / EN 61439-1 section 10.10.4.2.1c. IEC 61439 / EN 61439-1 section 5.3.2 Rated current of a circuit I nc "The I nc is the value of the current that can be carried by this circuit loaded alone, under normal service conditions. " Example:
MCCB If an operating current (I B ) is specifi ed, the rated current of the installed device must be calculated. If no operating current (I B ) is specifi ed, an installation device is selected and the rated current of the circuit (I nc ) is calculated. It results from the division of the operating current and the factor 0.8 according to IEC 61439 / EN 61439 Example operating current: 180 A 180 A: 0.8 = 225 A The rated current of the installed device must be at least 225 A. The next size for MCCB is 250 A. Example device selection: MCCB: 250 A 250 A x 0.8 = 200 A The maximum rated current of the circuit I nc is 200 A. The rated current of the circuit I nc is 200 A.
23 Selection of the installed device of outgoing circuits based on the rated current of the circuits I nC Example 1: WITH specifi ed operating current of the load Example 2: WITHOUT specifying the operating current of the load