Step 2: Design of an assembly and design verification Determining the operating current (I B ) I nc x assumed loading factor = I B The operating current I B is necessary to detect the permissible thermal rise (power dissipation). The operating current (I B ) can be specifi ed. If no operating current (I B ) is specifi ed, it is calculated according to the formula. Thereby, in addition to the already determined rated current of the circuit (I nc ), also the number of circuits is taken into account. As shown in Table 101, an asseumed loading factor for the calculation of the operating current (I B ) may be used depending on the number of circuits.
The operating current I B is calculated according to the formula: I B = I nc x assumed loading factor I nA The I B is calculated according to the formula: I B = I nc x assumed loading factor The customer specifi es the rated operating current I B. The assumed loading factor from Table 101 may be used. Example Operating current: 180 A Example Number outgoing circuits: 3 Assumed load factor: 0.9 I nc = 200 A 200 A x 0.9 = 180 A The operating current I B is 180 A. I B = 180 A The operating current I B is 180 A.
I B = 180 A 24 Table 101 from IEC 61439 / EN 61439 Assumed load factor Number of outgoing circuits Mi distribution board IEC 61439-2 / EN 61439-2 ENYSTAR distribution board IEC 61439-3 / EN 61439-3 2-3 0.9 0.8 4-5 0.8 0.7 6-9 0.7 0.6 10 or more 0.6 0.5 Determination of the operating current I B Example 1: WITH specifi ed operating current Example 2: WITHOUT specifying the operating current