HiPhi — 2016 Guide IEC EN61439 en 98171000 5 2016

Step 2: Design of an assembly and design verification Calculation of the power dissipation (P V ) The permissible power dissipation P V for the entire assembly is calculated from the difference of - installed power dissipation through installed device, busbars and wiring and - power dissipation of the enclosures in the form of heat emission. The determination of the power dissipation is quick and easy with the HENSEL calculation tool. ONLINE at www.hensel-electric.de/61439 ONLINE calculation tool HENSEL "Design verifi cation of permissible temperature rise".

Design verifi cation of permissible temperature rise according to IEC 61439-1 / EN 61439-1 Section 10.10 The tool automatically calculates the installed and dissipated power dissipation, and where appropriate, the RDF. ONLINE at www.hensel-electric.de/61439 After entering the data for installed device, busbar system and used enclosures, the calculation tool automatically determines the installed and dissipated power and, where appropriate, the RDF. The result is the difference of installed and dissipated power dissipation. It can be positive or negative. With a positive difference , the permissible temperature rise of the assembly is verifi ed.

In case of a negative difference , there is a risk of overheating. This can be prevented by selecting larger or additional enclosures and thus the dissipated power dissipation is increased. A further possibility is the reduction of the installed power dissipation. Since the number of installed device cannot be reduced, a computational reduction of the power dissipation can be performed by applying the rated diversity factor (RDF). Online via internet www.hensel-electric.de/61439 O w w 25