Step 2: Design of an assembly and design verification Determining the rated diversity factor (RDF) Specifi ed operating current If the operating current (I B ) is specifi ed and not calculated, formula 1 can be used to determine the rated diversity factor (RDF). With a positive difference of installed and dissipated power dissipation, the rated diversity factor (RDF) is equal to the assumed loading factor. Calculated operating current If the operating current (I B ) is calculated, the rated diversity factor (RDF) is determined via the power dissipation (P V ).
With a negative difference , the HENSEL calculation tool automatically calculates the rated diversity factor (RDF) according to formula 2. IEC 61439 / EN 61439 -1 Section 5.4 Rated diversity factor RDF (Rated Diversity Factor) Formula 1: RDF = I B I nc RDF = assumed loading factor x dissipated power dissipation installed power dissipation Formula 2:
"The rated diversity factor is the per unit value of the rated current, assigned by the assembly manufacturer, to which outgoing circuits of an assembly can installed p p di i ti x l be continuously and simultaneaously loaded taken into account the mutual thermal influences." With a positive difference, the RDF corresponds to the assumed loading factor. The customer specifi es the operating current I B. With a negative difference, the RDF must be determined by means of a calculation . For this purpose, the values from the calculation tool for dissipated power dissipation and installed power dissipation are used. This value is used in Formula 1.
RDF = I B according to customer specifi cation I nc RDF = assumed loading factor x dissipated power dissipation installed power dissipation p p x installed di i ti l Example: I B =180 A and I nc = 200A Example: Result from the calculation table is 0.9. RDF = 180 A = 0.9 200A RDF = 0.9 RDF = 0.9 Online via internet www.hensel-electric.de/61439 O w w The ONLINE calculation tool from HENSEL provides the design verifi cation of permissible temperature rise in a safe, fast and easy way. The tool automatic- ally calculates the installed and dissipated power dissipation and, where appropriate, the RDF.
The tool provides the design verifi cation of permissible temperature rise according to IEC 61439-1 / EN 61439-1 Section 10.10 as a PDF fi le. 26 Determining the rated diversity factor RDF Example 1: WITH specifi ed operating current Example 2: WITHOUT specifying the operating current