Step 3: Assembly / manufacture of the distribution board Assembly instructions for distribution board systems HENSEL supports the manufacture and assembly of a distribution board with extensive assembly instructions. PASSION FOR POWER. ENYSTAR distribution boards up to 250 A with doors intended to be operated by ordinary persons (DBO) according to IEC 61439-3 / EN 61439-3 Assembly instruction ENYSTAR Distribution Boards up to 250 A Intended to be operated by ordinary persons (DBO) in accordance with IEC 61439-3 The modular structure of enclosures in grid of 90 mm allows a free configuration of the outer form. Combinable in all directions to follow given requirements on site.
ENYSTAR Assembly ENYSTAR System design 1 Enclosure depth with hand operation Positioning of enclosures Assembly of enclosures according to layout Different enclosure depths allow the installation of equip- ment of different heights. With an extension frame the depth of the enclosure sizes 3 and 4 can be extended by 50 mm. 2 4 with tool operation 186 3 Extension frame for extending installation depths by 50 mm with hand operation with tool operation Removal of the frames with door Unscrew and remove the frame from the bottom part together with the door. Operation Clear separation of the operation areas for unskilled persons and access/opera- tion areas for skilled persons (electricians).
Download at www.hensel-electric.de/61439 „ Hand operated doors in areas to which unskilled persons have access for oper- ating devices „ Locking facilities with keys prevent the unauthorized opening of doors 8 9 „ Standard tool operation for slotted screwdrivers and triangle (option square, double bit) ENYSTAR Assembly Closing Plates, Flanges, Cable Insert ENYSTAR Assembly Cable inserts, Box Fin ENYSTAR Wiring Terminals ENYSTAR Wiring Closing walls via closing plates Insert closing plates into openings of outer walls of the distribution board and fix them with enclosure connectors. Installation of cable inserts Saw the box fin.
Afterwards the cable insert is mounted and fixed via enclosure connectors and the rubber entries can be inserted. Direct connection of conductors to busbars Capacity of terminals for direct busbar connection see Hensel Catalogue. For busbar boxes with covers for the combination with fusegear and blanking strips Wiring Strip Strip at the connection point by a suitable length. Direct connection of copper conductor with terminal KS 150 Terminals for direct busbar connections for cables and laminated wiring strip Hint: For observance of insulation resistance clearances of 10 mm are necessary between different potentials and of 15 mm between conductive metal parts.
Type KS 16 F KS 35 F KS 70 F KS 150 F ENYSTAR Accessories Width Width PE N Right: First bend forward wiring strip by 180° and then 90° to the side. Cable entry - opening knockouts in flanges Knock out the appropriate cable entries within flanges with screwdriver. Adjust stepped grommet on the cable diameter. Wiring or connection module AM RK 150 to busbar. * Prior to connection, aluminium conductors must be prepared according to the appropriate technical re- commendations, see technical information Aluminium conductors. KS 240/12 AM RK 150 Connection module 35-150 mmІ for the installation in busbar boxes with covers 5-pole space units: 8 L1-L3, N: 35-150 mmІ Cu PE: 10-70 mmІ Cu 250 A:
Mi VS 250 160 A: Mi VS 160 12 x 5 mm 12.0 Nm L1-L3, N 10.0 Nm PE conductors round conductors RE (round single) SE (sector, solid) RM (round stranded) SM (sector, stranded) RE (r r single) ound ound sol (solid) s (stranded) sol (solid) sector-type conductors sector conductors SE (sector International short forms of types of conductors In tern a t ion al s solid) -type r , r (rigid) f (fl exible) r (rig round conductors sector-type conductors fl exible conductors Wiring strip In order to adjust differences in height, bend a step. Insert cable and fix it with the cable ties.
Assignment of terminals for direct busbar connection to cross sections and enclosures with electrical functions Electrical connections 100 A up to 250 A from busbars to electrical equipment Cable glands Insert cable gland into the appropriate knockout and fasten with lock nut. Insert the cable into the box from the front. Box fin provides an easier wiring across two boxes. Wiring strip Mi VS ... Insulation cover for busbars Attach cover for insulating busbars if necessary. Saw out fin in box wall. Insert box fin and fix via fixing wedges. Connection of wiring strip Mi VS ... with terminal for direct busbar connection KS ...
Terminals for direct connection on busbars Closing of enclosure walls with flanges for cable entry Direct connection of wiring strip Mi VS ... to electrical equipment with flat contact M 10 with wiring terminal VA 400 Terminal for connection of wiring strips Mi VA ... Mi SA 1210 Insert flanges for cable entry into open outer walls of the distribution board and fix them with enclosure connectors. A wide range of flanges for the cable entry is available. Connection of cables to devices with flat contact M 10 with terminal for direct connection DA 185 Example: Wiring with wiring strip Mi VS 250, terminals for direct connection on busbars and strip- connection terminals VA 400.
N P Terminal for direct connection DA 185 12 13 26 27 Assembly instruction ENYSTAR for download: www.hensel-electric.de/61439 A w w 30 sCeacbtlieo ncross-Tcoypned uocf torWiring stripFor busbarsTtoigrqhuteening 16 mm11 mm 3L2L1 LNPE 3L2L1 1,5-16 mm2Cu ... x 5 mm4 Nm 21 mm 3L2L1 LNPE 410-3-750 m mmm22CCuu 111106060000 AAAA:::: MMMMiiii VVVVSSSS 111106060000...... xx 55 mmmm61 0N Nmm 34 mm34 mm 3355--125400 mmmm22CCuu//AAlluu**250 A: Mi VS 25011112222 xxxx 5115 00 mm mmmm mm //1420 NNmm E -L3, N 144 mm 3L2 L1 L NPE