HiPhi — 2016 Guide IEC EN61439 en 98171000 5 2016

Installation and ambient conditions Installation areas and degree of protection, condensation, system design HENSEL supports the manufacture and assembly of a distribution board with extensive assembly instructions. PASSION FOR POWER.

Assembly instruction Mi Power Distribution Boards up to 630 A Power switchgear and controlgear assemblies (PSC) in accordance with IEC 61439-2 Mi Power switchgear and controlgear assembly (PSC) according to IEC 61439 -2 / EN 61439-2 Assembly lid hinges, wall openings, assembly of enclosures, fl anges, cable entry, cable insertion, extension frame, box fi n Mounting wall mounting, fl oor-standing, measures against condensation forming, canopy Device installation mounting plate, DIN rails, PE and N terminals, protection against access to hazardous parts/covers Wiring busbar systems, connecting terminals, wiring, bending wiring strips, feed-in terminals, FIXCONNECT ® plug-in terminals, connection of aluminum conductors Download at www.hensel-electric.de/61439 Routine tests of switchgear assemblies routine verifi cation / inspection / report, marking, initial inspection before putting installation into operation and inspection periods, declaration of conformity Assembly of Mi distribution boards according to assem- bly draft Mi Distribution Boards Assembly Wall Opening, Assembly of enclosures Connections of cables Connect cables strain-relieved and pressure-relieved.

Mi Distribution Boards Assembly Flanges, Cable Entry Direct connection of conductors to busbars Mi Distribution Boards Wiring Terminals Mi-Verteiler Zubehцr Mi-Verteiler Zubehцr Pre-assembled and tested enclosures with electrical functions Cable entry Close knockouts/openings for the cable entry accord- ing to the specified degree of protection. Capacity of terminals for direct busbar connection see HEN- SEL Catalogue. Mi DK KV Sammelschienen-Direktanschlussklemmen fьr Leiter und lamelliertes Verdrahtungsband Hinweis: Zur Einhaltung der Isolationsfestigkeit sind zwischen unterschiedlichen Potentialen 10 mm und zu inaktiven, leitfдhigen Metallteilen 15 mm Luftstrecke einzuhalten.

Typ Leiter- querschnitt Leiterart Verdrahtungs- band fьr Sammel- schienen Anzugs- dreh- moment KS 16 F 1,5-16 mm 2 Cu - ... x 5 mm 4 Nm 11 mm 1) KS 16 Z 1,5-16 mm 2 Cu - ... x 10 mm 4 Nm 11 mm KS 35 F 4-35 mm 2 Cu 100 A: Mi VS 100 160 A: Mi VS 160 ... x 5 mm 6 Nm 16 mm 1) KS 35 Z 4-35 mm 2 Cu 100 A: Mi VS 100 160 A: Mi VS 160 ... x 10 mm 6 Nm 16 mm 1) KS 70 F 10-70 mm 2 Cu 100 A: Mi VS 100 160 A: Mi VS 160 ... x 5 mm 10 Nm 21 mm 1) KS 70 Z 10-70 mm 2 Cu 100 A: Mi VS 100 160 A: Mi VS 160 ... x 10 mm 10 Nm 21 mm 1) KS 120 F 25-120 mm 2 Cu 250 A: Mi VS 250 400 A: Mi VS 400 ... x 5 mm 20 Nm 25 mm 1) Breite 250 A N: 12x5 L1-L3: 12x10 PE:

12x5 Mi-Sicherungsgehдuse Diazed/Neozed Mi-NH-Sicherungsgehдuse, Sicherungs– elemente und Sicherungslasttrennschalter Mi-Sammelschienengehдuse 400 A N: 12x10 L1-L3: 20x10 PE: 12x5 1) 1) 1) 1) 1) 1) 1) 630 A N: 25x10 L1-L3:30x10 PE: 12x10 250 A N: 12x5 L1-L3: 12x10 PE: 12x5 1) 1) 1) 400 A N: 12x10 L1-L3: 20x10 PE: 12x5 630 A N: 25x10 L1-L3:30x10 PE: 12x10 250 A N: 12x5 L1-L3: 12x10 PE: 12x5 400 A N: 12x10 L1-L3: 20x10 PE: 12x5 630 A N: 25x10 L1-L3:30x10 PE: 12x10 Mi DK KV Knock out of box walls for electrical connection and cable entry Flanges Attach flanges by means of 4 wedge links and 1 clamp to the box wall. Right:

Covering of cable entry with cable entry cover Wiring 346 347 * Aluminiumleiter mьssen vor dem AnschlieЯen entsprechend den einschlдgigen technischen Empfehlungen vorbereitet werden, siehe technische Information Aluminiumleiter. KS 120 Z 25-120 mm 2 Cu 250 A: Mi VS 250 400 A: Mi VS 400 ... x 10 mm 20 Nm 25 mm 1) KS 240/12 Cu 35-240 mm 2 KS 150 35-150 mm 2 Cu 630 A: Mi VS 630 12 x 5 mm / 12 x 10 mm 20 Nm 34 mm KS 185 95-185 mm 2 Cu/Alu* - 20 x 10 mm / 25 x 10 mm / 30 x 10 mm KS 240 V - - 630 A:

Mi VS 630 20 x 10 mm / 25 x 10 mm / 30 x 10 mm KS 300 120-300 mm 2 Cu/Alu* - 20 x 10 mm / 25 x 10 mm / 30 x 10 mm Alu 35-185 mm 2 Cu / Alu* - 12 x 5 mm / 12 x 10 mm 40 Nm 34 mm 30 Nm 38 mm 30 Nm 38 mm 30 Nm 38 mm 1) Klemmen im Lieferumfang der Funktionsgehдuse, siehe Gehдusebeschreibungen. runde Leiter sektorfцrmige Leiter runde Leiter sektorfцrmige Leiter r (rigid) = starr f (fl exible) = fl exibel mit gasdicht verpresster Aderendhьlse sol (solid) = eindrдhtig s (stranded) = mehrdrдhtig Internationale Kurzbezeichnung der Leiterarten 1) 1) Box walls are knocked out for the electrical connection within the distribution board.

For the assembly of the enclo- sures, the appropriate open- ings of the wedge joints are knocked out as well. Assignment of terminals for direct busbar connection to cross sections and enclosures with electrical functions. Electrical connection 100 A up to 630 A from busbars to electrical equipment. Assembly of boxes For sealing the boxes in posi- tion, a self-adhesive gasket is stuck to the box wall (applies to closed box walls, too). Cable entry Knock out the appropriate cable entries within flanges or box walls with screwdriver. Wiring strip from laminated copper, insulated, supplied length 2 meters. The box assembly is carried out by a wedge connection.

To increase stability, press wall clamps onto the box fins. Connection of wiring strip Mi VS ... with terminal for direct busbar connection KS ... Wiring strip Mi VS ... Terminals for direct connection on busbars Use a wall separator for sub- dividing 300 mm box walls into two 150 mm walls for flange or box mounting. Cable glands Insert cable gland into the appropriate knockout and fasten with lock nut. Direct connection of wiring strip Mi VS ... to electrical equipment with flat contact M 10 with wiring supply ter- minal for direct connection of laminated copper wiring strip Mi VA ... Terminal for connection of wiring strips Mi VA ...

Connection of cables to devices with flat contact M 10 with terminal for direct connection DA 240. Example: Wiring with wiring strip Mi VS 400, terminals for direct connection on busbars and wiring strip connection terminals VA 400. Terminal for direct connection DA 240 10 11 21 Assembly instruction Mi for download: www.hensel-electric.de/61439 A w w 31