HiPhi — 2016 Guide IEC EN61439 en 98171000 5 2016

Routine verification / inspection Example: Mi Distribution Board 1. Degree of protection of cabinets / enclosures 5. Internal electrical circuits and connections The manufacturer must specify measures that must be implement- ed to maintain the designated degree of protection. Check that seals and covers have been installed according to the manufacturer's instructions. Conductors must be checked for consistency with circuit diagrams and bolted connections have to be checked at random. 2. Creepage and clearance distances 7. Mechanical operation (actuating elements, lockings) The clearances between different potentials should be greater than the values given in Table 1 of the standard.

We recommend a mini- mum distance of 10mm. The effectiveness of mechanical actuating elements, interlocks and locks including those associated with removable parts must be checked. 8. Dielectric properties 3. Protection against electric shock and integrity of the pro- tective circuits The protective circuits must be subjected to a test for integrity of electrical connection. A power-frequency withstand test must be performed on all circuits for a period of 1 second, as per IEC/EN 61439-1 section 10.9.2. The test voltage for switchgear assemblies with a rated insulation voltage between 300-690 V a.c. is 1.890 V.

The test values for different rated insulation voltages are given in Table 8 of IEC/EN 61439-1. 33