Electrical equipment 6.3 Protection against electric shock Fault loop impedance To ensure that protective devices can trip within the specified time period, the fault loop impedance shall be such that the following condition is met: Since the measurements are taken at ambient temperature and at low currents, the increase in resistance of the conductors as a result of the increase in temperature due to the fault current shall be taken into account. The following condition applies: Note Evaluation according to IEC 60364 If Z S (n) > 2/3 Ч U 0 /I a , a more precise assessment should be performed according to IEC 60364-6:2006, Annex C.61.3.6.2.
Control Panels compliant with IEC Standards and European Directives 116 Reference Manual, 10/2017, A5E38284819002A/RS-AB/002 ZS is the impedance of the fault loop comprising the source, the live conductor up to the point of the fault and the protective conductor between the point of the fault and the source Ia is the current that produces automatic disconnection of the protective device within the specified time U0 is the nominal AC voltage to ground Zs(n) = measured or calculated value of ZS under normal conditions The value U0 is generally known as a characteristic of the given type of grounding system. Example:
TN-S system 400 V phase/phase → U0 = 230 V phase/ground Ia is specified by the manufacturer of the protective device used. It is the minimum current that causes the short-circuit release of a protective device to respond.