HiPhi — 6.4.1.1 Arrangement of overcurrent protective devices

Electrical equipment 6.4 Design and protection of equipment Short-circuit current at the installation location The electrical equipment shall be designed for both the highest possible short-circuit current and the lowest possible short-circuit current. The major factor here is the prospective short- circuit current. Highest possible short-circuit current If no separate supply terminals are used, the largest possible short-circuit that can occur within the control panel builder's area of responsibility (see Fig. 6-1 (Page 82)) is the 3-pole short-circuit on the outgoing side of the supply terminal or of the supply disconnecting device.

Calculating the maximum short-circuit values at the location in which the overcurrent protective devices are installed involves a significant amount of engineering work. Equipment manufacturers design most overcurrent protective devices for high short circuits. For this reason, it is common practice to dimension all overcurrent protective devices according to the prospective short-circuit current at the incoming supply point. Furthermore, overcurrent protective devices shall ensure the protection of control devices such as contactors or frequency converters against any damage. Siemens specifies the appropriate overcurrent protective devices in the relevant manuals of the control devices.

Example Simplest method: Design every overcurrent protective device for 50 kA. Figure 6-31 Design of overcurrent protective devices according to the maximum prospective short- circuit current at the incoming supply point. Control Panels compliant with IEC Standards and European Directives 124 Reference Manual, 10/2017, A5E38284819002A/RS-AB/002