HiPhi — 6.4.1.4 Selection of control devices

Electrical equipment 6.4 Design and protection of equipment Excerpt from the Compact Operating Instructions "SINAMICS G120C low-voltage inverters" Types of coordination according to IEC 60947 The types of coordination describe the foreseeable reaction of a switching device in the event of a short circuit. IEC 60947-4-1 distinguishes between types of coordination "1" and "2" for motor starters and switching devices. Both types of coordination are based on the requirement that "(...) the contactor or starter shall cause no danger to persons or installation under short-circuit conditions".

Type of coordination 1 According to the aforementioned standard, the contactor or starter "(...) may not be suitable for further service without repair and replacement of parts." For the machine this means: Contactor and/or overload relay is/are possibly defective. Components may possibly be unsuitable for further service. Operator and machine protection are unsafe in the event of continued service. Functionality of components is uncertain. ⇒ The components should be replaced. Advantage The costs of manufacturing the control panel are lower than with type of coordination 2 because smaller switching devices can be used.

Disadvantage Long downtimes High outlay for repairs Control Panels compliant with IEC Standards and European Directives 136 Reference Manual, 10/2017, A5E38284819002A/RS-AB/002