HiPhi — 6.4.1.5 Conductor dimensioning

Electrical equipment 6.4 Design and protection of equipment No. of loaded circuits The current-carrying capacity of the cable (I z ) also depends on the number of loaded circuits in the cable duct. Tables D.2 and D.3 of the standard show the relevant correction factors for so-called "Grouping". Table 6- 8 Grouping correction factors Source: IEC 60204-1, excerpt from Table D.2: Derating factors for I Z for grouping Note Number of circuits Table D.2 in the standard refers to the number of circuits, not to the number of conductors. With three-phase loads, for example, there would be six conductors with two three-phase circuits.

Control Panels compliant with IEC Standards and European Directives 142 Reference Manual, 10/2017, A5E38284819002A/RS-AB/002 Methods of installation (...) (see Note 3) Number of loaded circuits/cables 2 4 6 9 B1 (conductors or single-core cables) and B2 (multicore cables) 0.80 0.65 0.57 0.50 C, single layer with no gap between cables 0.85 0.75 0.72 0.70 E, single layer on one perforated tray without gap between cables 0.88 0.77 0.73 0.72 E, as before but with 2 to 3 trays, with a vertical spacing between each tray of 300 mm (see Note 4) 0.86 0.76 0.71 0.66 Control circuit pairs ≤ 0.5 mm2 independent of methods of installation 0.76 0.57 0.48 0.40 NOTE 1: These factors are applicable to:

– cables, all equally loaded, the circuit itself symmetrically loaded; – groups of circuits of insulated conductors or cables having the same allowable maximum operating temperature; NOTE 2: The same factors are applied to: – groups of two or three single-core cables; – multicore cables. NOTE 3: Factors derived from IEC 60364-5-52:2009. ...