Electrical equipment 6.4 Design and protection of equipment 6.4.1.6 Practical example The information relating to selection of equipment on the previous pages is explained further by the following practical example. Step 1: Selection of protection and switching devices from configuration manual P = 15 kW, U = 400 V I n = 29 A Excerpt from the manual "Configuring SIRIUS Innovations" Step 2: Dimensioning the cable According to current-carrying capacity during normal operation According to overload condition According to short-circuit condition Dimensioning according to current-carrying capacity during normal operation Assumption: Ambient air temperature = 45 °C No.
of loaded circuits in cable duct = 2 Method of installation of cable = B1 (single-core cable in cable duct) PVC cable Control Panels compliant with IEC Standards and European Directives Reference Manual, 10/2017, A5E38284819002A/RS-AB/002 147