Electrical equipment 6.5 Equipotential bonding The continuity of the protective conductor shall be ensured wherever electrical equipment is fitted on exposed conductive parts such as lids, doors or cover plates. It is advisable to use a protective conductor. If this is not possible, fastenings, hinges or sliding contacts designed to have a low resistance shall be used. Note Verification of the continuity of the protective conductor is mandatory in accordance with IEC 60204-1. For more information, see Chapter Verification of the continuity of the protective bonding circuit (Page 196).
Where cables are exposed to damage, for example flexible trailing cables, the continuity of the conductors shall be ensured by means of appropriate measures, for example by monitoring. Conductor wires, conductor bars or slip-ring assemblies that are part of the protective bonding circuit shall not carry current under normal operating conditions. This means that both the protective conductor (PE) and neutral conductor (N) shall have their own conductor wires or slip-ring. The continuity of the protective conductor (PE) shall be ensured by appropriate measures, e.g. by doubling the current collectors or monitoring the continuity.
Rule Note Protective bonding circuit The protective bonding circuit shall never be interrupted. For this reason, it is not permissible to incorporate a switching device or an overcurrent protective device, e.g. circuit breaker, miniature circuit breaker, fuse, in the protective bonding circuit. Exception Links for test or measurement purposes that cannot be opened without the use of a tool and that are located in an enclosed electrical operating area. Plug/socket combinations, removable current collectors or other devices that can interrupt the protective bonding circuit shall have a first make last break contact.
This will ensure that the equipment is always effectively grounded while current is flowing. → First ground and then contact, or disconnect first before interrupting the ground connection. The continuity of the protective conductor shall be easily comprehensible. The bonding points for protective conductors may only be used to connect protective conductors and shall be labeled/marked accordingly. Only one protective conductor may be connected per bonding point. The following options are permitted:
Symbol according to IEC 60417-5019 (preferred solution) Identification by the bicolor combination GREEN-AND-YELLOW Control Panels compliant with IEC Standards and European Directives 166 Reference Manual, 10/2017, A5E38284819002A/RS-AB/002