HiPhi — 6.6.3 Selection criteria

Electrical equipment 6.6 Conductors and cables Selection according to connection to equipment Another selection criterion is specified by the manufacturer. These specifications can normally be found in the product data sheets. As part of the device approval process, the cables and their cross-sectional areas are determined according to the following criteria: 1. Short-circuit withstand rating The combination of device and connected cables shall be capable of withstanding the short-time thermal and mechanical stresses imposed by the short-circuit current for which the device is to be approved. The r.m.s. value of the short-circuit current is an equivalent for the thermal stress.

The temperature reached as a result of this thermal stress shall not exceed the maximum short-time temperature of the cable. The peak value of the short-circuit current is an equivalent for the mechanical stress; the connecting terminals and the specified torque shall be capable of keeping the connected conductors securely clamped when subjected to this stress. 2. The nominal current of the device The combination of device and connected cables shall not exceed the maximum operating temperature of the cables, connecting terminals or the device when the nominal current is flowing continuously. 3.

The mechanical construction of the device and the connection points at the devices It is not possible to connect flexible busbars to some devices. Causes: The forces transferred to the device by the copper ribbon cables during a short circuit are too high. Their operating temperature is too high. They are not clamped securely enough by the connecting terminals. Note Flexible connection bars If you are using flexible connection bars, then compare their connection data with the data of the device! Control Panels compliant with IEC Standards and European Directives Reference Manual, 10/2017, A5E38284819002A/RS-AB/002 175