Electrical equipment 6.9 Testing and verifications Figure 6-73 Example: 3RV20314JB10 tripping characteristic (excerpt from SIMARIS curves) If it is impossible to guarantee tripping within the specified disconnecting times, one of the following two measures shall be implemented: Additional protective bonding to reduce the hazardous touch voltage to below 50 V. Selection of a faster overcurrent protective device in order to ensure disconnection within the required time period.
You will find further information in Chapter "Protection against electric shock", Section Fault protection (Page 110) Conclusion This comparison should always be performed for each feeder that contains an overcurrent protective device. For reasons of efficiency, however, it is in practice sufficient to carry out the comparison for only those circuits that are obviously critical. The longer the cable and the smaller its cross-sectional area, the higher the impedance and thus the longer the disconnecting time. Control Panels compliant with IEC Standards and European Directives Reference Manual, 10/2017, A5E38284819002A/RS-AB/002 201