HiPhi — 7.2 Main circuit - molded case circuit breakers

Devices in the control panel and the machine environment 7.2 Main circuit - molded case circuit breakers 7.2 Main circuit - molded case circuit breakers 3VA molded case circuit breakers Molded case circuit breakers are used in power distribution systems and machine control panels for line, personnel and motor protection and for disconnecting loads. Molded case circuit breakers are very frequently used as supply disconnecting devices for machinery. Molded Case Circuit Breakers (MCCB) are also known as compact current limitting circuit breakers. They are described in product standard IEC 60947-2.

Selection criteria A user shall at least know the following criteria in order to select the correct molded case circuit breaker: 1. For what purpose will the molded case circuit breaker be used: line (system) protection, motor protection, starter protection, as switch disconnector? 2. Number of poles: 1 / 2 / 3 / 4 poles? 3. Desired mounting type: Fixed-mounting / plug-in technology / draw-out technology? 4. Nominal current for Siemens MCCBs: I n (16 A to 1600 A)? 5. Breaking capacity I cu ? 6. Required tripping method: Thermal-magnetic (TMTU = thermal magnetic trip unit) or electronic (ETU = electronic trip unit)?

This criterion depends on requirements regarding selectivity and on the required setting options for protection parameters. 7. Communication: Will it be necessary to transmit data? If so, which data? What are the data for? Which bus system will be used? etc. Molded case circuit breakers as line protection The 3VA molded case circuit breaker is part of an extensive portfolio of line and generator protection products. All of the following benefits are combined in the MCCB, type 3VA:

Thermal-magnetic trip unit (TMTU) in 2 sizes up to 250 A Smallest molded case circuit breaker (MCCB) on the market up to 160 A (at 70 kA, I CU =I CS ) Electronic trip unit (ETU) in 3 sizes up to 1000 A Wide power range Small footprint Uniform accessories platform across all 3VA molded case circuit breakers Metering function integrated in the ETU 8-series Optional communication interface via PROFIBUS, PROFINET, Modbus TCP, Modbus RTU with the ETU 5-series and 8-series Control Panels compliant with IEC Standards and European Directives Reference Manual, 10/2017, A5E38284819002A/RS-AB/002 239