Devices in the control panel and the machine environment 7.3 Main circuit - contactors Contactors for special applications (for resistive loads) (3RT23) Components that convert electricity into heat are always switched on and off by contactors for resistive loads. Examples are: Electric heaters, heating tunnels used for drying paint in the automotive industry, heating systems in trains. Figure 7-8 Contactors for resistive loads Contactors for capacitive loads (capacitor contactors) (3RT26) Capacitor contactors are often installed in transformer stations. Transformers or capacitors draw high currents during the precharging phase before they reach their normal operating state.
The precharging resistors in the capacitor contactor limit the high precharging currents to prevent them from causing damage to the normal switching contacts. This means that capacitor contactors used for this kind of application have a significantly longer service life than normal motor contactors. Figure 7-9 Capacitor contactors Contactor relays (3RH21) Contactor relays are used to distribute control signals. They are often chosen as a means of increasing the number of contacts in complex installations. This may become necessary, for example, if the line contactor does not have enough contacts.
Unlike the line contactor, the contactor relay does not switch the load, but controls a line contactor that switches the load. Control Panels compliant with IEC Standards and European Directives Reference Manual, 10/2017, A5E38284819002A/RS-AB/002 243