Use of IE2 and IE3 motors 8.3 Use of switching devices and protective equipment with IE3 motors Special considerations for motors with high starting currents For motors with high starting currents in particular, soft starters are especially suitable since the high starting currents are reduced to lower values and the supply network is therefore subject to a comparatively lower load. Using soft starters to limit the starting current of motors with high starting currents can have different effects. This applies only if the other conditions for startup, such as the load conditions, do not change as well:

Case A Motors that have higher starting currents but also an improved torque curve can be started under comparable conditions under certain circumstances. In this case, it is not necessary to analyze the startup process any further because other aspects of starting rarely need to change under ideal conditions. Case B Motors that consume higher starting currents but exhibit no changes in torque behavior in comparison to standard motors shall be provided with more energy during startup. In Case B, the effects on startup shall be analyzed more closely: the diagram shows how the startup current over time can change when motors with higher starting currents are used.

A motor with normally high starting current ratios (5 to 8 times the rated motor current) is taken as the starting point. ① Normal ② Starting current higher ③ Starting time longer Control Panels compliant with IEC Standards and European Directives Reference Manual, 10/2017, A5E38284819002A/RS-AB/002 307 Startup diagram Startup time Starting current Application ① Normal condition Normal Normal The resulting starting torque is sufficient for correct power-up of the motor. ② Higher starting current Normal Higher The resulting starting torque cannot be reduced any further because, for example, the acceleration resulting from a high load torque is not sufficient and the motor does not start up.

③ Longer starting time Longer Normal The resulting starting torque can be reduced slightly further since sufficient acceleration is available.