Control engineering - definition of terms and fundamental principles 5.2 Types of grounding system 5.2 Types of grounding system TN-S system T = Terra = directly grounded neutral N = low-resistance return conductor to transformer neutral point S = separate conductors for PE and N Advantage: System conforms with EMC guidelines Disadvantage: 5 conductors TN-C system T = Terra = directly grounded neutral N = low-impedance return conductor to transformer neutral point c = a "combined" conductor for PE and N = PEN Advantage: Only 4 conductors Disadvantage:
Susceptible to electromagnetic interference because harmonics are discharged via the PEN which means that loads with N conductor are additionally stressed by harmonics. TN-C-S system With this system, a combined N and PE (PEN) conductor exits from the transformer, but at some point, the PEN conductor is split up into separate PE and N lines. PEN is nonetheless the correct description for this PE because the neutral can be separated out of the combined conductor at any time. Once the neutral has been separated out of the combined conductor, it cannot be connected to the PEN again, i.e. it must be a "spur line"!
If a neutral conductor that had already been split from the PEN were reconnected to it, it would constitute a parallel connection with an incalculable impedance and thus also an incalculable short-circuit load. Furthermore, it can result in undesirable stray ("vagrant") currents. Figure 5-1 TN-C-S system Control Panels compliant with IEC Standards and European Directives Reference Manual, 10/2017, A5E38284819002A/RS-AB/002 47