Control engineering - definition of terms and fundamental principles 5.11 Utilization categories Utilization categories for contactor relays Utilization categories for contactor relays according to IEC 60947-5-1 Alternating current AC-12 Control of resistive loads and inductive loads with isolation by optocouplers AC-13 Control of solid-state loads with transformer isolation AC-14 Control of small electromagnetic loads ( AC-15 Control of electromagnetic loads (> 72 VA) DC current DC-12 Control of resistive loads and solid-state loads with isolation by optocouplers DC-13 Control of electromagnets DC-14 Control of electromagnetic loads having economy resistors in circuit Utilization categories for switch disconnectors Utilization categories for switch disconnectors with and without fuses according to EN 60947-3 Table 5- 3 Utilization categories for switch disconnectors Source:
EN 60947-3 Switch disconnectors with and without fuses, Table 2:
Utilization categories Category A = Frequent use; Category B = Occasional use Control Panels compliant with IEC Standards and European Directives Reference Manual, 10/2017, A5E38284819002A/RS-AB/002 63 Nature of current Utilization categories Typical applications Category A Category B Alternating current AC-20A* AC-20B* • Connecting and disconnecting under no-load conditions AC-21A AC-21B • Switching of resistive loads including moderate overloads AC-22A AC-22B • Switching of mixed resistive and inductive loads, including moderate overloads AC23-A AC23-B • Switching of motor loads or other highly inductive loads Direct current DC-20A* DC-20B* • Connecting and disconnecting under no-load conditions DC-21A DC-21B • Switching of resistive loads including moderate overloads DC-22A DC-22B • Switching of mixed resistive and inductive loads, including moderate overloads (e.g.
shunt motors) DC23-A DC23-B • Switching of highly inductive loads (e.g. series motors) * The use of these utilization categories is not permitted in the USA.