Control engineering - definition of terms and fundamental principles 5.12 Switch disconnectors and circuit breakers Requirements of circuit breakers for line protection Requirements of circuit breakers for motor protection Control Panels compliant with IEC Standards and European Directives Reference Manual, 10/2017, A5E38284819002A/RS-AB/002 65 Must trip within two hours at 1.3 x load. (This tripping time is one hour for devices up to 63 A). Must not trip within two hours at 1.05 x load. Usual setting ranges: Adjustability of the overload release is not necessary in most cases.
Response values of the short-circuit releases 5 - 10 * Ir A selectivity evaluation makes sense for applications involving power distribution boards. Must trip within two hours at 1.2 x load. (This tripping time is one hour for devices up to 63 A). Must not trip within two hours at 1.05 x load. Insensitivity to motor starting inrush current normally about 20 ms. Optional: Phase failure sensitivity to protect explosion-proof motors Temperature compensation (-20 °C …
+60 °C) Thermal memory (several starting attempts cause temperature rise in motor) → prompt restart conditionally possible, without thermal memory ⇒ long delay Adjustable trip class for adjusting breaker to motor's starting behavior.