Control engineering - definition of terms and fundamental principles 5.19 Motor duty types Periodic duty In periodic duty with very short times de-energized and at rest, the thermally effective current may occasionally exceed the effective load current of the motor. This is generally the case if the period of operation and time de-energized and at rest of the motor are relatively short because the starting currents then affect the temperature rise. Annex E (Figure E6) of IEC 61439-1 contains the following method of calculating this thermal equivalent.
t 1 Starting time at I 1 t 2 Run time at I 2 t 3 t 1 + t 2 + t 3 Interval time at I 3 = 0 = cycle time Figure 5-15 Calculation of average heating effect Control Panels compliant with IEC Standards and European Directives Reference Manual, 10/2017, A5E38284819002A/RS-AB/002 79