Electrical equipment 6.2 Incoming supply conductor termination and supply disconnecting device Example Breaking capacity of supply disconnecting device ≥ current of largest motor when stalled + the sum of all other loads = 6 x 30 A + 20 A + 15 A = 215 A Figure 6-7 Example: Dimensioning of supply disconnecting device / main disconnect Note (Rated) breaking capacity ≠ rated operational current The (rated) breaking capacity should not be confused with the rated operational current. With a circuit breaker, the (rated) breaking capacity is the maximum short-circuit current that can be disconnected.
With a switch disconnector, a (rated) breaking capacity is also usually indicated on the data sheet. Control Panels compliant with IEC Standards and European Directives Reference Manual, 10/2017, A5E38284819002A/RS-AB/002 89