HiPhi — 6.2.2 Supply disconnecting (isolating) device

Electrical equipment 6.2 Incoming supply conductor termination and supply disconnecting device Operating means of the supply disconnecting device The operating means of the supply disconnecting device shall be easily accessible and shall be external to the enclosure of the electrical equipment and located between 0.6 m and 1.9 m above the servicing level. Recommendation: An upper limit of 1.7 m. Exception: Circuit breakers with a motorized operating mechanism need not be provided with a handle outside the electrical equipment enclosure where other means (e.g. pushbuttons) are provided to open the supply disconnecting device outside the enclosure.