Electrical equipment 6.2 Incoming supply conductor termination and supply disconnecting device 6.2.5 Devices for isolating electrical equipment Voltage poses another potential hazard. In other words, if the voltage itself is the agent which poses a potential hazard, devices for isolating electrical equipment or parts thereof shall be provided. These devices shall meet the following conditions: They are easy to operate and access. They are suitable for the intended use. They are readily identifiable as to which part(s) or circuit(s) they serve. The supply disconnecting device may, in some cases, be capable of acting as an isolating device.
Separate isolating devices are required only when it is necessary to work on individual parts of the electrical equipment of a machine, or on one of a number of machines fed by a common wire system or conductor bar system or inductive power supply system. Devices which also serve as a supply disconnecting device (Page 86) may be used. Note Disconnectors, withdrawable fuse links and withdrawable fuse isolating links shall always be located in an electrical operating area. Information to this effect shall be supplied with the electrical equipment. Devices without isolation function shall not be used for this purpose.
Control Panels compliant with IEC Standards and European Directives 98 Reference Manual, 10/2017, A5E38284819002A/RS-AB/002