Chapter 7: Maintenance 1. Open the robot object editor. 2. Select Configure > Safety Settings > Verify ESTOP Hardware Delay , then click Next. 3. Enable high power, if not already enabled, then click Next. 4. Press an E-Stop button (on the Front Panel), then click Next. The utility will confirm that the hardware delay has been verified for this robot, and dis- play the delay times for channels A and B. Teach Restrict Configuration Utility This utility sets the hardware Teach Restrict maximum speed parameter to factory spe- cifications. NOTE : Ensure that the commissioning jumper is plugged into the XBELTIO jack on the eAIB before you start this procedure. Procedure NOTE :
This procedure takes 2 or 3 minutes to complete. From within the ACE software: 1. Open the robot object editor. 2. Select Configure > Safety Settings > Configure Teach Restrict , then click Next. 3. From the Prerequisite screen, click Next. The wizard will go through all of the robot's motors, and display messages that it is con- figuring Channel A and B for each. It will then record the configuration, and display the target times that it set. 4. Click Finish. 5. Reboot the eAIB. 6. If you are using an optional SmartController EX, reboot it. On some systems, the SmartController EX will reboot automatically.
Teach Restrict Verification Utility This utility verifies that the Teach Restrict parameters are set correctly and that the hardware Teach Restrict maximum speed control is working. This is a two-part wizard. The first is run in Auto mode. The second is run in Manual mode. Before running this verification utility, the Teach Restrict must be configured. NOTE : If the commissioning jumper is plugged into the XBELTIO jack on the eAIB, remove it before you start this procedure. Hornet 565 Robot User's Guide, 14608-000 Rev C Page 128 of 156