Chapter 7: Maintenance Figure 7-21. eAIB Commissioning Jumper l A pendant is required for the Teach Restrict verification. E-Stop Configuration Utility This utility sets the E-Stop hardware delay to factory specifications. NOTE : Ensure that the commissioning jumper is plugged into the XBELTIO jack on the eAIB before you start this procedure. Procedure From within the ACE software: 1. Open the robot object editor. 2. Select Configure > Safety Settings > Configure ESTOP Hardware Delay , then click Next. This procedure will configure Channel A and then Channel B. It will then report the delay that it set for each. 3. Reboot the eAIB. 4.
If you are using an optional SmartController EX, reboot it. On some systems, the SmartController EX will reboot automatically. E-Stop Verification Utility This utility verifies that the hardware E-Stop parameters are set correctly and that the hard- ware E-Stop is working. The hardware E-Stop must have already been configured for this wizard to run. NOTE : If the commissioning jumper is plugged into the XBELTIO jack on the eAIB, remove it before you start this procedure. Procedure From within the ACE software: Hornet 565 Robot User's Guide, 14608-000 Rev C Page 127 of 156