omron — 2. Wiring

2. Wiring Power Supply Short-circuit bar *1 For Single-phase. Use R/L1 and S/L2. Forward RUN/STOP Reverse RUN/STOP External Fault (no contact) Fault RESET Grounding Multi-Step Speed Ref. 1 Multi-Step Speed Ref. 2 JOG Command Fault Multi-function Contact Output 250 VAC, 1 A or less *2 30 VDC, 1 A or less Shield connection terminal Multi-function Photocoupler Output +48 VDC, 50 mA or less Pulse Train Input Reference Pulse Train (max. 33 kHz) Frequency Setting Power Supply (+12 V, 20 mA) Frequency Setting 0 to 10 V (20 kOhm) 4 to 20 mA/0 to 20 mA (250 Ohm) Digital Operator Frequency Setting Potentiometer MEMOBUS Communications RS-485/422 max.

19,2 kbps Analog Monitor Output 0 to +10 VDC (2 mA) Terminal Resistance (1/2 W, 120 Ohm) Output Frequency Analog Monitor/Pulse Monitor selectable Shielded twisted-pair cable Shielded Only basic insulation (protective class 1, overvoltage category II) is provided for the control circuit terminals. Additional insulation may be necessary in the end product to conform to CE requirements. *1. Short-circuit bar should be removed when connecting a DC reactor. *2. Minimum permissible load: 5 VDC, 10 mA (as reference value). Contact Output Control circuit terminals Ground terminals Main circuit terminals EN-5 DC Reactor T optional) O erminal verload Relay Braking Resistor (optional)