3. Control Circuit Terminals EN-6 Symbol Name Function Signal Level Input S1 Multi-function input 1 Set by parameter n50 Default setting: Forward/Stop Photo-coupler Insulation, 8 mA at 24 VDC Note: NPN is the default setting for these terminals. No external power supply is required. Refer to connections shown on the following page. S2 Multi-function input 2 Set by parameter n51 Default setting: Reverse/Stop S3 Multi-function input 3 Set by parameter n52 Default setting: External fault. S4 Multi-function input 4 Set by parameter n53 Default setting: Fault Reset. S5 Multi-function input 5 Set by parameter n54 Default setting:

Multi-stop speed reference 1 S6 Multi-function input 6 Set by parameter n55 Default setting: Multi-stop speed reference 2 S7 Multi-function input 7 Set by parameter n56 Default setting: JOG command SC Sequence input common Common for S1 through S7 RP Master speed reference train input Pulse train input signal Max. 33 kHz FS Frequency Reference power supply DC power supply for frequency reference setting 20mA at 12 VDC FR Frequency Reference Input Input terminal for frequency reference setting 0 to10VDC 20kΩ FC Frequency Reference common Common for frequency reference use 4 to 20 mA 0 to 20 mA Output MA Multi-function output: NO Set by parameter n57 Default setting: Fault Relay output 1A max.

at 30 VDC and 250 VAC MB Multi-function output: NC MC Multi-function output common Common for MA and MB use P1 Photo-coupler output 1 Set by parameter n58 Default setting: RUNNING Photo-coupler output , 50A max at +48VDC P2 Photo-coupler output 2 Set by parameter n59 Default setting: FREQUENCY AGREED PC Photo-coupler output common Common for P1 and P2 AM Analogue Monitor output Set by parameter n65 Default setting: output frequency 2mA max. at 0 to 10VDC. AC Analogue Monitor common Common for AM use