Tags and the Project Database • Min field: Specify a minimum value for the tag in engineering units. This tag is accessible during runtime. • Max field: Specify maximum value for the tag in engineering units. This tag is accessible during runtime. • Unit field: Type any string (up to 9 characters) as a brief description or reference of the tag. This tag is accessible during runtime. • Signal Conditioning area • Dead Band checkbox: Click (check) to insert the dead band value of a tag. Dead band value is a variation around a central value of the tag, which is not recognized for alarms. • Smoothing checkbox: Click (check) to reduce the rate of change for the tag's values.
Use only for integers and real tags. For example, if you select the Smoothing option for the LEVEL1 tag containing the value = 50. Then in the next search, if the LEVEL1 changes to 60, the system will store the average of 50 + 60 in the database, so the new value = 55. Boolean-Type Tag Parameters Note: For descriptions of these parameters, see String-Type Tag Parameters above. See also: Using Tag Properties: Alarms , Using Tag Properties: History Using Tag Properties: Alarms Use the Tag Properties dialog to view the configured alarms for a selected tag. IWS disables this command if there are open alarm worksheets. Before using these dialogs, you should have already created the alarm groups.
ALARM TYPES: • HiHi : A Very High alarm is present. • Hi : A High alarm is present. • Lo : A Low alarm is present. • LoLo : A Very Low alarm is present. • Rate : An alarm based on rate of change is present. • Deviation : An alarm based on deviation from a given set point is present. Example: • If SetPoint = 50, Deviation + = 5, Deviation − = 5, and Deviation Dead Band = 0.5; • IWS generates an alarm when the temp ≥ 55 or temp ≤ 45; and • A return to the normal occurs when temp ≤ 54.5 or temp ≥ 45.5. ALARM LIMITS: • HiHiLimit : When creating Very High alarms in the Tag Properties dialog, use this field to specify the limits.
You can access this field during runtime and use it during modifications on the fly. • HiLimit : When creating High alarms in the Tag Properties dialog, use this field to specify the limits. You can access this field during runtime and use it during modifications on the fly. • LoLimit : When creating Low alarms in the Tag Properties dialog, use this field to specify the limits. You can access this field during runtime and use it during modifications on the fly. • LoLoLimit : When creating Very Low alarms in the Tag Properties dialog, use this field to specify the limits. You can access this field during runtime and use it during modifications on the fly. • DevSetpoint :
Reference point for a tag value deviation that triggers an alarm. Define the alarm message in the Tag Properties dialog or on an Alarm worksheet. You can access this field during runtime. • Dev+Limit : Limit deviation to a value higher than the DevSetpoint in a tag value that triggers an alarm. Define the alarm message in the Tag Properties dialog or on an Alarm worksheet. You can access this field during runtime. • Dev+Limit : Limit deviation to a value lower than the DevSetpoint in a tag value that triggers an alarm. Define the alarm message in the Tag Properties dialog or on an Alarm worksheet. You can access this field during runtime. InduSoft Web Studio Page 119