Tags and the Project Database Page 124 InduSoft Web Studio Tag Property Description R or R/ W Data Type Available on Data Type… Retain Bool Int Real Str DevM If 0, the Deviation- alarm is not active. If 1, the DevM alarm is active. R Boolean N Y Y N n/a AlrStatus Integer value with the status of the current active alarms associated to the tag. Each bit of this integer value indicates a specific status: • Bit 0 (LSB): HiHi Alarm active • Bit 1: Hi Alarm active • Bit 2: Lo Alarm active • Bit 3: LoLo Alarm active • Bit 4: Rate Alarm active • Bit 5: Deviation+ Alarm active • Bit 6: Deviation- Alarm active Examples: If Tag>AlrStatus returns the value 2, it means that "Hi" alarm is active.
If it returns the value 3, it means that the "HiHi" and the "Hi" alarm are active simultaneously. If this property returns the value 0, it means that there are no active alarms associated to this tag. For Boolean tags, only the values 1 (bit 1), 4 (bit 2) or 16 (bit 4) can be returned. R Integer Y Y Y N N Ack This property can have two values: • 0: There are no alarms associated with this tag that require acknowledgment. • 1: There is at least one alarm associated with this tag that requires acknowledgment. This works as a global acknowledge for the tag and goes to 0 only when all alarms for the tag have been acknowledged. R Boolean Y Y Y N N UnAck This property can have two values: • 0:
There is at least one alarm associated with this tag that requires acknowledgment. • 1: There are no alarms associated with this tag that require acknowledgment. If you manually set this value to 1, then the active alarms (if any) are acknowledged. The value of this property is always the opposite of the Ack property. R/W Boolean Y Y Y N N AlrAckValue Text associated with the Acknowledged state of a Boolean tag. This text is displayed in the Value column of an Alarm/Event Control. You can also edit this text in the Tag Properties dialog (Alarms – Bool Type). R/W String, up to 32 chars Y N N N Y AlrOffValue Text associated with the Normalized state of a Boolean tag.
This text is displayed in the Value column of an Alarm/Event Control. You can also edit this text in the Tag Properties dialog (Alarms – Bool Type). R/W String, up to 32 chars Y N N N Y AlrOnValue Text associated with the Active state of a Boolean tag. This text is displayed in the Value column of an Alarm/Event Control. R/W String, up to 32 chars Y N N N Y