Tags and the Project Database Note: • If a property is marked "n/a" with regards to being retentive, it's because the property is inherent in the tag definition (e.g., Name, Size) or the value of the property is continuously derived during runtime (e.g., alarm activation, DisplayValue). To enable retention for a tag, select the Retentive Parameters option in the Tag Properties dialog . • If the project attempts to write a value outside of the range specified in the Min and Max properties, the Tags Database will not accept the new value and a warning message is written in the Output window.
If both Min and Max properties are configured with the value 0 (zero), it means that any value applied to the tag type will can be written to the tag. • You cannot use tag properties (such as Bit fields) to configure Alarm or Trend worksheets. • Although you can apply tag properties to System Tags , those properties will not persist when you download your project to a CE device. InduSoft Web Studio Page 125 Tag Property Description R or R/ W Data Type Available on Data Type… Retain Bool Int Real Str You can also edit this text in the Tag Properties dialog (Alarms – Bool Type). AlrDisable This property can have two values: • 0: The alarms associated with this tag are enabled.
This means that when an alarm condition occurs, the alarm will become active. • 1: The alarms associated to this tag are disabled. This means that even if an alarm condition occurs, the alarm will not become active. R/W Boolean Y Y Y N N