omron — Email Settings for Alarm Worksheet

Data Logging and Display EMAIL SETTINGS FOR ALARM WORKSHEET IWS has the ability to send emails automatically when alarm events occur. The emails are sent using the standard SMTP (Simple Message Transfer Protocol). Therefore, you just need a valid email account with a SMTP Server and POP3 server — it is not necessary to install any additional software, such as Microsoft Outlook. Important: Before being email to send emails, it is necessary to execute successfully the CnfEmail function (from the built-in language) at least once. This function sets the email account parameters used when sending emails from the project (e.g., SMTP server, user name, password, and so forth).

Alarms Worksheet — Email Settings Page 220 InduSoft Web Studio Field Remarks Syntax • Acknowledgement: Alarm active and acknowledged • Normalization: Alarm no longer active and not acknowledged. Field Remarks Syntax Enable send automatic email Name of the tag associated with the alarm. Checkbox To, Cc, Bcc Target addresses to whom the emails will be sent. You can configure multiple email addresses in each box (To, Cc and/or Bcc) by separating the addresses with the semi-colon character ( ; ). Text and/or {Tag} (up to 1024 chars) Subject When selecting "Use alarm message", the alarm message itself is used as the subject of the email to be sent.

When selecting "Custom", you can configure a custom text to be used as Subject when sending the alarm. Radio-button / Text (up to 1024 chars) Send 1 message per email When checking this option, each alarm is sent in an individual email and all emails are sent when the Send Trigger is triggered. Otherwise, all alarm messages are buffered and sent in only one email when the Send Trigger is triggered. You cannot disable (uncheck) this option when the Subject option is configured with "Use alarm message".

Checkbox Remove failed messages from the buffer When checking this option, the emails are removed from the buffer after attempting to send them, even if there was an error (failure) and the email was not sent. Otherwise, the messages are kept in the buffer until they are sent successfully or when the buffer reaches its maximum size. checkbox Send email when alarm is Allow you to configure which alarm events should generate emails: • Active: When the alarm becomes active. • Ack: When the alarm is acknowledged. • Norm: When the alarm is normalized. Notice that each event can be enabled/disabled individually.

checkbox Current Status The tag configured in this field, if any, is updated with the current status of the current or last email that the project attempted to send: • -2: Incorrect version of the INDMail.DLL library. • -1: The INDMail.DLL library is corrupted. • 0: SendEmailExt function is not being executed. • 1: Sending email(s) Tag