Data Logging and Display ADVANCED SETTINGS FOR ALARM WORKSHEET Alarm Worksheet, Advanced Settings Dialog The following table describes the Advanced settings on an Alarm worksheet : InduSoft Web Studio Page 221 Field Remarks Syntax • 2: Last email was sent successfully. • 3: There was an error sending the last email. Current Error The tag configured in this field, if any, is updated with the error message describing the result of the last email that the project attempted to send. Therefore, when configuring a tag in this field, this tag must be a String type. Tag Message Format This interface allows you to configure the actual format of the message sent by email, based on the alarm event(s):
• Day, Month, Year, Hour, Minute, Second, MS: The options checked will compose the timestamp for the alarm messages. MS stands for milliseconds. • Items: The options checked will compose the email message for each alarm. You can configure the order of the items, by using the Move Up and Move Down buttons. • Separator: Allow you to choose the separator used between the items checked in this interface. While you configure these settings, the Sample field displays an example of the format of the message according to the settings being configured. Checkbox and Radio-button Send Trigger When the alarm events are generated, they are kept in an internal buffer (memory).
When the tag configured in this field changes of value, the email(s) on the internal buffer are sent to the addresses configured in the To, Cc and Bcc fields. After being successfully sent, the emails are removed from the internal buffer. Tag Max buffer size Maximum number of alarm messages (events) that can be stored in the internal buffer simultaneously. When this limit is reached, the buffer follows a FIFO (First- In, First-Out) behavior, discharging the older messages as soon as the newer messages are generated, guaranteeing that the buffer does not exceed the limit configured in this field.
Tag or Number Buffer size The tag configured in this field, if any, is updated with the number of messages (events) currently stored in the internal buffer. Tag Clear Buffer When the tag configured in this field changes of value, all messages (events) currently stored in the buffer are deleted. These messages will never be sent. Tag Disable send When the value of the tag configured in this field is TRUE, the Email feature is temporarily disabled. Alarm events generated while the Email feature is disabled will not be stored in the internal buffer. Also, emails will NOT be sent in this condition, even if the tag configured in the field Send Trigger changes of value.
Tag Field Remarks Syntax Disable When the value of the tag configured in this is TRUE, all alarms configured in this group are temporarily disabled. This option is useful to disable alarms under special conditions (e.g., during maintenance). Tag Total Alarms The tag configured in this field, if any, is updated with the number of alarms from this group, which are currently active. Tag