omron — Alarm Worksheet Body

Data Logging and Display Alarm Worksheet Body The following table describes the Body settings on an Alarm worksheet : Page 222 InduSoft Web Studio Field Remarks Syntax Total Unack The tag configured in this field, if any, is updated with the number of alarms from this group, which are currently active AND have not been acknowledged yet. Tag Remote Ack Trigger When the tag configured in this field change of value, all active alarms from this group are acknowledged. This option can be used to acknowledge alarms regardless of any action from the operator.

Tag Dead Band Time > Activation Each alarm must remain continuously in its alarm condition for the period of time specified in this field before becoming active. This option is useful to avoid generating alarms on intermittent conditions (e.g., noise). If this field is left in blank, the alarm becomes active as soon as its condition is true. Tag or Number Dead Band Time > Normalization Each alarm must remain continuously out from its alarm condition for the period of time specified in this field before becoming normalized. This option is useful to avoid normalizing alarms on intermittent conditions (e.g., noise).

If this field is left in blank, the alarm become normalized as soon as its condition is no longer true. Tag or Number Dead Band Time > Time Stamp/Value Each alarm maintains a time stamp of the last significant activity, along with the value of the tag at that time. You can select the type of activity that updates the time stamp: • Activation/Norm (default): The time when the dead band ended — that is, when the alarm becomes activated or normalized. • Last Tag Change: The time when the value of the tag last changed during the dead band. • Start Condition: The time when the dead band started. Combo Field Remarks Syntax Tag Name Name of the tag associated with the alarm.

Tag Type Type of the alarm: • HiHi: Activates the alarm if the tag value is equal or higher than the limit. • Hi: Activates the alarm if the tag value is equal or higher than the limit. (For Boolean tags, if the value is 1.) • Lo: Activates the alarm if the tag value is equal or lower than the limit. (For Boolean tags, if the value is 0.) • LoLo: Activates the alarm if the tag value is equal or lower than the limit. • Rate: Activates the alarm if the tag value varies faster than the rate specified to the alarm. (For Boolean tags, if the value changes.) • DevP: Activates the alarm if the tag value is equal or higher than the Set Point tag plus the limit. • DevM:

Activates the alarm if the tag value is equal or lower than the Set Point tag minus the limit. When using the types Rate, DevP and DevM, it is necessary to configure additional settings by the Tag Properties dialog (Properties on the Home tab of the ribbon). Combo-box Limit Limit associated with each alarm. The limits can be modified dynamically during runtime, by the tag fields HiHiLimit, HiLimit, LoLimit, LoLoLimit, Rate, DevP and DevM (e.g., TagLevel- >HiLimit). Number