Data Logging and Display For example, if you specify a Dead Band value = 5 for a tag value = 50 and the tag value changes to 52, the system will not register this variation in the event log file, because the variation is less than 5. However, if the tag value change is equal to or greater than 5, the system will save the new value to the history file. • Message column: Type a string (message) related to this tag change. You can specify tags in messages using the {tag name} syntax. The Tags parameter can be useful if you want to generate a log file of events that are not necessarily alarm conditions (for example, Motor On , Motor Off , and so forth). Setting the Event Database 1.
On the Project tab of the ribbon, in the Settings group, click Options . The Project Settings dialog is displayed: Project Settings: Options Tab 2. In the Alarm History and Events pane, click the arrow to the right of the History Format field. Select Database . 3. Click the Event Database button. This opens the Database Configuration dialog . Enter the applicable data in this window. Click OK when you are done. 4. Click OK to save the Project Settings data and close the window. Event Table on a Relational Database The fields saved in the History Event are described in the following table:
Page 228 InduSoft Web Studio Field Name Data Type Remarks Version Integer This field is created only when the File Format is Proprietary. Current version: 002 Event Type _ Integer 1: SECURITY SYSTEM 2: DISPLAY 3: RECIPE 4: REPORT 5: CUSTOM MESSAGES 6: SYSTEM WARNING 7: LOG TAGS Event Time _ TimeStamp Timestamp indicating when the event occurred. When the File Format is Proprietary, IWS saves the Event Time in the following format: MM/ DD/YYYY HH:MM:SS.MSS. Event Info _ String Tag Name