Data Logging and Display The dialog in detail Advanced dialog The Advanced dialog contains the following elements: InduSoft Web Studio Page 253 Area / Element Name Description Run Mode Options Update trigger When the tag configured in this field changes value, the trend object is updated (refreshed). Update interval When the update trigger is issued and the X Axis if of type numeric, the value on this field will be added to the minimum and maximum values of the X Axis. Load indicator Type the name of a project tag. While the trend control is loading external data, the tag receives a value of 1, and when the trend control has finished loading the data, the tag receives a value of 0.
Move to current time on run When this box is checked, X axis shifts to the current time automatically when the object is triggered to Play mode, during runtime. Retrieve bounding samples When this box is checked, the object retrieve the data outbound the object (first points only). Uncheck this option can improve the performance, since the points outbound the object will not be retrieved from the history. On the other hand, the object will not draw lines linking the first and last samples to the extremities of the object. Run-Time Config Save trigger The settings of the Trend object modified during runtime can be saved in temporary files. This option can be used to:
• Keep the settings consistent, so when the user closes the screen and opens it again, or re-starts your project, the settings configured during runtime are not lost. • Create standard settings for different scenarios and load the appropriate configuration during the runtime, based on a pre-defined condition or based on the user-selection. When the tag configured in this field changes value (e.g., toggles), the current settings of the Trend object are saved in the temporary file. This command is not available for the Thin Client.
Load trigger When the tag configured in this field changes value (e.g., toggles), the settings from the temporary file are loaded and applied to the Trend object during runtime. Note: After the screen where the Trend object is configured is saved, the settings are not automatically loaded from the temporary file when the screen is opened again, unless the Load trigger command is executed before the screen is closed. File Name If this field is left blank, the temporary file is saved in your project's Web sub-folder with the syntax ScreenNameObjectIDTrendControl.stmp (e.g., MyScreen10TrendControl.stmp).
The Thin Client station saves/loads the temporary file in the standard Temp directory of the operating system (e.g., \Documents and Settings\CurrentUser\Local Settings\Temp). You can configure a customized file name for the temporary file in this field or even configure a string tag between curly brackets, so the user can change the name of the configuration file dynamically during runtime by changing the value of this tag. If you do not specify any path, the file is saved in your project's Web sub-folder by default.
Auto Save When this box is checked, the current settings of the Trend are automatically saved in the temporary file when the screen where the Trend is configured is closed during runtime. If the box is not checked, the settings are saved only when the Save trigger command is executed. Custom Point Selection Screen This interface allows you to create your custom dialog to modify or insert pens to the object.