Creating a New Project • Enable ToolTips checkbox: Click to enable this box, to display the ToolTips configured on the objects of the screens when viewing them on the Thin Client (web browser). • Auto Screen Scaling checkbox: Click to enable this box, to automatically scale screens displayed in a web browser window. Using this option, the screen fits to the size of the web browser window, regardless of its resolution. Note: The Auto Screen Scaling option is not valid for Web browsers running under Windows CE operating systems. • Enable File Compression checkbox: Click to enable this box to compress the files stored on the Web sub- folder of your project folder.
This option is useful for reducing download time, particularly if you have a slow connection between your server and the Thin Client. • Log ( Enable checkbox and FileName text field): Click to enable the checkbox, and type a file name into the text field to generate a log file on the Thin Client station. You can use this log file for debugging purposes. • Virtual Keyboard : When this option is checked, the Virtual Keyboard is enabled for your project running Thin Clients. The keyboard allows the user to enter data during runtime on touchscreen panels — that is, without typing on a physical keyboard.
For example, a Text object with the Text Data Link animation applied and the Input Enabled option checked. You can establish a default configuration for the virtual keyboard: • Default : Select the default keyboard type to be used in your project, when no keyboard type is specified by the calling object or function. • Scale : Using this option, you can shrink or enlarge the keyboard to fit the size of the target display. A value of 100% represents the default size of each keyboard type. • Show Hint checkbox and field: When this option is checked, a hint is displayed in the title bar of the keyboard. For objects, the hint is configured in the Object Properties dialog .
Otherwise, enter a string or string Tag in the Show Hint field to serve as a defaut hint. • Show Min/Max Fields option: When this option is checked, the minimum and maximum allowed values are displayed at the bottom of the keyboard. For objects, these values are configured in the Object Properties dialog . Otherwise, the Min and Max properties of the associated Tag are used by default. Note: The Min and Max fields are displayed only on the Keypad keyboard type, and only when the associated Tag is defined as Integer or Real. If Min is greater than Max, then input will be disabled.
If Min/Max configured on the object is different from Min/ Max configured in the Tag properties, then your project will attempt to scale the input accordingly. IP Security Settings IP Security button: Click this button to open the IP Security dialog. IP Security dialog Use the parameters on this dialog to specify the range of IP addresses for the computers that are allowed to access your project as Thin Clients. This option is useful when you can control the IP Address of the Thin Client computers allowed to connect to the Web server. Click the Enable checkbox, and when the Edit pane parameters become active, type IP addesses in the From and To fields to specify the IP address range.
Use the Add and Remove buttons to move the IP addresses into the IP Address Range list. When a Thin Client attempts to connect to the server, it checks for an IP address Page 86 InduSoft Web Studio