ISPSoft User Manual ABS/REL mode: Relative Mode increases or decreases based on the current coordinates. Absolute Mode increases or decreases based on the absolute coordinates as target position. Relative mode (Symbol/Address) increases or decreases based on the current coordinate address, symbol or address are allowed. Absolute mode (Symbol/Address) increases or decreases based on the absolute coordinates as target position, symbol or address are allowed. Target position: Target coordinate. For ABS/REL mode , the options include symbol/address. Target speed : Maximum speed of the target. ACC/DEC time: The time to reach target speed and stop. Completion action:
Go to next segment to complete the data and continue to the next. Completion refers to an end once data is complete. Completion flag (I/M) : When the data execution is complete, set the register to ON. The register range is set as M0~M8191 or I510~I519 only when Completion action is set to Completion . No. of next segment: Continue with the next data number, not limited to the same assigned axis number. But, take note that the same axis number cannot output more than 2 numbers from the table or output position command at the same time. When Completion action is set to Completion , the number is automatically continued to the next segment Notice for table input: 1.
The PLC will automatically run at the set speed when the target speed or the Acc\Dec time is set to 0. The objective position cannot be set to 0 in the relative mode. The objective positions of two adjacent row numbers cannot be set to the same value in the absolute mode. 2. I number can be used more than once. Users must determine through which row number the I number can be completely outputted. 3. The instruction which the start table outputs is API2718 TPO. API2720 TPWL can be used to modify the output parameters while PLC is running. 23-12