5.9 o: Operator Related Settings 5.9 o: Operator Related Settings These parameters concern the various functions and features of the digital operator. u o1: Display Settings and Selections These parameters determine how data is shown on the operator display. n o1-02: User Monitor Selection after Power Up Selects which monitor parameter will be displayed upon power up. Defaulted to show the frequency reference when the drive is first turned on. Setting 1: Frequency Reference (U1-01) Setting 2: Forward/Reverse Setting 3: Output Frequency (U1-02) Setting 4: Output Current (U1-03) n o1-03:
Digital Operator Display Selection Parameter o1-03 allows the programmer to change the units used in the following parameters and monitors: • U1-01: frequency reference • U1-02: output frequency • d1-01 to d1-08: frequency references Setting 0: Hz The frequency reference and monitors are displayed in Hz with a resolution of 0.01 Hz. Setting 1: % The frequency reference and monitors are displayed as a percentage with a resolution of 0.01%. 100% is equal to the maximum output frequency. u o2: Operator Key Selections These parameters determine the functions assigned to the operator keys. n o2-02:
STOP Key Function Selection Selects if the STOP key on the digital operator can be used to stop the operation when the drive is controlled from a remote source (i.e., not from digital operator). Setting 0: Disabled The STOP key has no function when the drive is controlled by a source other than the digital operator. The drive can only be stopped from the Run command source that has been selected. Setting 1: Enabled The STOP key can be used to terminate the operation, even if the Run command source is not assigned to the digital operator. If operation has been interrupted by pressing the STOP key, the Run command must be cycled to restart the drive. n o2-04:
Drive Model Selection Parameter o2-04 matches the control board to the drive hardware. Proper setting of o2-04 is important for optimal performance and proper protection for the drive hardware. This parameter is configured at the factory and does not normally require adjustment in the field. It is available primarily to accommodate control board replacement in the event of damage. 112 SIEP C710606 33A OYMC AC Drive – J1000 User Manual No. Name Setting Range Default o1-02 User Monitor Selection after Power Up 1 to 4 1 No. Name Setting Range Default o1-03 Digital Operator Display Selection 0 to 1 0 No. Name Setting Range Default o2-02 STOP Key Function Selection 0 or 1 1