Lithium NG 51,2V battery manual 4.7. Charger settings The recommended charging parameters for the charging sources are: For 12.8V models : 14.2V absorption voltage, 2 hours absorption time and 13.5V float voltage For 25.6V models: 28.4V absorption voltage, 2 hours absorption time and 27.0V float voltage For the 51.2V model: 56.8V absorption voltage, 2 hours absorption time and 54.0V float voltage For the recommended charge currents, please see the Charging the battery and recommended charger settings [18] chapter and refer to the table in the Technical data [30] chapter.
For more information on the charging settings of the individual chargers or inverters/chargers, please refer to the manuals on the respective product page. Adjusting charging voltages is not required for DVCC-controlled inverters/chargers and chargers such as the Orion XS and MPPT solar chargers. This setting is automatic and slightly different from a manual setting. For more information about DVCC, see your GX device manual on the respective product page . Once all connections have been made, the system wiring needs to be checked, the system needs to be powered up, and the BMS functionality needs to be checked. Follow this checklist: 4.8.
Commissioning Check the polarity of all battery cables. Check the cross-sectional area of all battery cables. Check if all battery cable lugs have been crimped correctly. Check if all battery cable connections are tight (don’t exceed maximum torque). Tug slightly on each battery cable and see if the connections are tight. Check all BMS cable connections and make sure the connector screw rings are screwed all the way down. Connect the system positive and negative DC cable to the battery (or battery bank). Check the string fuse(s) rating (if applicable). Install the string fuse(s) (if applicable). Check the main fuse rating. Install the main fuse.
Check if all battery charge sources have been set to the correct charge settings. Turn on all battery chargers and all loads. Check if the BMS is powered up. Disconnect a random BMS cable and verify that the BMS is turning off all charge sources and all loads. Reconnect the BMS cable and check if all charge sources and loads turn back on. Page 16 Installation