Victron Energy Lithium NG 51,2V — 6.1.4. Less capacity than expected

Lithium NG 51,2V battery manual 6.1.3. How to recover an imbalanced battery Charge the battery using a charger configured for lithium and controlled by the BMS. Be aware that cell balancing only occurs during the absorption stage. Each time the charger goes to float, it must be manually restarted. Rebalancing can take a long time (up to a few days) and requires many manual charger restarts. Be aware that it might look like nothing is happening during cell balancing. The cell voltages can remain the same for a long time, and the BMS will repeatedly turn the charger on and off. This is all normal.

Balancing takes place when the charge current is at or above 1.8A or when the BMS has temporarily disabled the charger. Balancing is almost finished when the charge current drops below 1.5A and the cell voltages are close to 3.55V. The rebalancing process is complete when the charge current has dropped even further, and all cells are 3.55V. Be 100% sure that the BMS controls the charger; dangerous cell overvoltage can occur if it is not. Check this by monitoring the cell voltages using the VictronConnect app. The voltage of the fully charged cells will slowly creep up until 3.7V has been reached. At this point, the BMS will disable the charger and the cell voltages will drop again.

This process will continuously repeat until the balance is restored. Calculation example of time required to restore a heavily imbalanced battery: Imagine a 12.8V 200Ah battery with one heavily undercharged (discharged) cell for this example. A 12.8V battery contains 4 cells, each with a nominal voltage of 3.2V. They are connected in series, resulting in 3.2 x 4 = 12.8V. Like the battery, each cell has a capacity of 200Ah. Let's say the imbalanced cell is only at 50% of its capacity while the other cells are fully charged. To restore the balance, the rebalancing process will need to add 100Ah to that cell.

The balancing current is 1.8A (per battery and all battery sizes, except for the 12.8V/50Ah model, which has a balancing current of 1A). Rebalancing the cell will take at least 100/1.8 = 55 hours. Balancing only takes place when the charger is in the absorption stage. If a 2-hour lithium charge algorithm is used, the charger will need to be manually restarted 55/2=27 times during the rebalancing process. If the charger is not restarted immediately, the balancing process will be delayed, and this will add to the total balancing time. A tip for Victron Energy distributors and professional users: To avoid having to restart the charger continuously, use the following trick.

Set the float voltage at 14.2, this will have the same effect as the absorption stage. Also, disable the storage stage and/or set that to 14.2V. Or alternatively, set the absorption time to a very long time. What matters is that the charger maintains a continuous 14.2V charge voltage during the rebalancing process. After the battery has been rebalanced, set the charger back to the normal lithium charge algorithm. Never leave a charger connected like this in a running system. Keeping the battery at such a high voltage will decrease the lifetime of the battery. 6.1.4. Less capacity than expected If the battery capacity is less than its rated capacity, these are the possible reasons for that:

The battery's cell imbalance causes premature low-voltage alarms, which in turn causes the BMS to turn loads off. Please refer to section How to recover an imbalanced battery [24] . The battery is old and is near its maximum cycle life. Check how long the system has been in operation, how many cycles the battery has gone through and to what average depth of discharge the battery has been discharged. A way to find this information is to look at the history of a battery monitor (if available). The battery has been discharged too deeply, and one or more cells in the battery are permanently damaged.

These bad cells will have a low cell voltage faster than the other cells, and this will cause the BMS to turn loads off prematurely. Has the battery perhaps been through a very deep discharge event? Page 24 Troubleshooting & support