Lithium NG 51,2V battery manual 3. System design and BMS selection guide This chapter describes how the battery interacts with the BMS and how the BMS interacts with loads and chargers to protect the battery. This information is important for system design and the selection of the most suitable BMS for the system. 3.1. Maximum number of batteries in series, parallel or series/parallel configuration A system can use up to 50 Victron Lithium NG batteries when configured with 12V or 24V batteries, and up to 25 batteries when using 48V batteries, regardless of the Victron BMS NG used.
This allows for energy storage capacities of up to 384 kWh with 24V batteries, 192 kWh with 12V batteries, and 128 kWh with 48V batteries, depending on the capacity and number of batteries used. See the Installation [10] chapter for installation details. Check the table below to see how the maximum storage capacity can be achieved (using 12.8V/300Ah, 25.6V/300Ah and 51.2V/ 100Ah batteries as an example): 3.2. The BMS alarm signals and BMS actions The battery itself monitors cell voltages, current and battery temperature.
The BMS constantly processes this data and, in addition to displaying it via the VictronConnect app and/or a GX device, creates warnings and alarms as needed, for example, when a low cell voltage is imminent or the battery temperature becomes too low to allow the battery to charge. To protect the battery, the BMS then switches off consumers and/or chargers or generates a pre-alarm in order to have enough time to take countermeasures. These are the possible battery warnings and alarms and the corresponding BMS actions: The battery communicates its data to the BMS via the BMS cables.
The BMS receives a low cell voltage from a battery cell If the system contains multiple batteries, all battery BMS cables are connected in series (daisy chained). The first and the last BMS cable is connected to the BMS. BMS The BMS receives a high cell voltage from a cell in a multiple-battery setup The battery is equipped with 50 cm long BMS cables. If these cables are too short to reach the BMS, they can be extended with BMS extension cables . There are two ways the BMS can control loads and chargers:
System design and BMS selection guide Page 4 System voltage 12.8V/300Ah Nominal energy 25.6V/300 Ah Nominal energy 51.2V/100Ah Nominal energy 12V 50 in parallel 192kWh na na na na 24V 50 in 2S25P 192kWh 50 in para llel 384kWh na na 48V 48 in 4S12P 184kWh 50 in 2S2 5P 384kWh 25 in parallel 128kWh BMS alarm signal BMS action Low cell voltage pre-alarm warning (≤ 3.0 V) The BMS generates a pre-alarm signal Low cell voltage alarm with a minimum delay of 30 seconds (≤ 2.8 V) The BMS turns loads off High cell voltage alarm (≥ 3.6 V) The BMS turns chargers off Low battery temperature alarm ( The BMS turns chargers off High battery temperature alarm (> 50 °C) The BMS turns chargers off BMS