Victron Energy Lithium NG 51,2V — 3.2.1. The BMS's pre-alarm signal

Lithium NG 51,2V battery manual 1. By sending an electrical or digital on/off signal to the charger or load. 2. By physically connecting or disconnecting a load or a charge source from the battery. Either directly or by using a BatteryProtect or Cyrix Li-ion relay . All available BMS types for the NG battery are based on either or both of these technologies. The BMS types and their functionality are briefly described in the next chapters. Load or charger Load or charger OFF signal BMS BMS The BMS sends an on/off signal to a load or charger The BMS connects or disconnects from a load or charger 3.2.1.

The BMS's pre-alarm signal The purpose of the pre-alarm is to warn that the BMS is about to turn off the loads because one or more cells have reached the cell undervoltage pre-alarm threshold (3.0 V, hardcoded). We recommend connecting the BMS's pre-alarm output to a visible or audible alarm device. When the pre-alarm is raised, the user can turn on a charger to prevent the DC system from shutting down. Switching behaviour In case of an imminent under-voltage shutdown, the BMS's pre-alarm output will switch on. If the voltage continues to decrease, the loads are switched off (load disconnect), and at the same time, the pre-alarm output will switch off again.

If the voltage rises again (the operator has enabled a charger or has reduced the load), the pre-alarm output will switch off once the lowest cell voltage has been increased above 3.2 V. The BMS ensures a minimum delay of 30 seconds between enabling the pre-alarm and the load disconnect. This delay allows the operator a minimal amount of time to prevent the shutdown. System design and BMS selection guide Page 5