© Siemens AG 2010 SIRIUS 3RW Soft Starters 3RW30, 3RW40 for Standard Applications 3RW40 SIRIUS 3RW40 for heavy starting (CLASS 20) 4 1) Stand-alone installation without auxiliary fan. 2) Soft starter with screw terminals: delivery time class } (preferred type). 3) Main circuit connection: screw terminals. Note: Selection of the soft starter depends on the rated motor current. Please observe the notes for the selection of soft starters on Page 4/7. The SIRIUS 3RW40 solid-state soft starters are designed for easy starting conditions. J Load Motor .In the event of devi- ating conditions or increased switching frequency, it may be necessary to choose a larger device.

Siemens recommends the use of the selection and simulation program Win-Soft Starter. For information about rated currents for ambient temperatures > 40 °C, see "Technical specifications". 4/17 Siemens LV 1 · 2010 * You can order this quantity or a multiple thereof. 3RW40 28-1BB14 3RW40 28-1TB04 3RW40 38-1BB14 3RW40 38-1TB04 3RW40 47-1BB14 3RW40 47-1TB04 Ambient temperature 40 °C Ambient temperature 50 °C Size DT Heavy starting (CLASS 20) PU (UNIT, SET, M) PS* PG Weight per PU approx.

Rated opera- tional cur- rent Ie1) Rated power of induction motors for rated opera- tional voltage Ue Rated opera- tional cur- rent Ie1) Rated power of induction motors for rated operational voltage Ue 230 V 400 V 500 V 200 V 230 V 460 V 575 V Order No. Price per PU A kW kW kW A hp hp hp hp Rated operational voltage U 200 ... 480 V2) e For DT etc. for the 3RW40 26-@@B@4 corresponding Order No.

see Selection and ordering data 3RW40 27-@@B@4 for normal starting • With screw or spring-type terminals 12.5 3 5.5 -- 11 3 3 7.5 -- S0 25 5.5 11 -- 23 5 5 15 -- S0 3RW40 26-@@B@4 3RW40 27-@@B@4 32 7.5 15 -- 38 11 18.5 -- 45 11 22 -- 29 7.5 7.5 20 -- S2 34 10 10 25 -- S2 42 10 15 30 -- S2 3RW40 36-@@B@4 3RW40 37-@@B@4 3RW40 37-@@B@4 63 18.5 30 -- 72 22 37 -- 58 15 20 40 -- S3 62 20 20 40 -- S3 3RW40 47-@@B@4 3RW40 47-@@B@4 Rated operational voltage U 400 ...

600 V e 3RW40 26-@@B@5 3RW40 27-@@B@5 • With screw or spring-type terminals 12.5 -- 5.5 7.5 11 -- -- 7.5 10 S0 25 -- 11 15 23 -- -- 15 20 S0 3RW40 26-@@B@5 3RW40 27-@@B@5 32 -- 15 18.5 38 -- 18.5 22 45 -- 22 30 29 -- -- 20 25 S2 34 -- -- 25 30 S2 42 -- -- 30 40 S2 3RW40 36-@@B@5 3RW40 37-@@B@5 3RW40 37-@@B@5 63 -- 30 37 58 -- -- 40 50 S3 3RW40 47-@@B@5 72 -- 37 45 62 -- -- 40 60 S3 3RW40 47-@@B@5 Order No. supplement for connection types • With screw terminals 1 • With spring-type terminals3) 2 Order No. supplement for thermistor motor protection • Standard function B • Thermistor motor protection only with rated control supply voltage Us 24 V AC/DC T Order No.

supplement for rated control supply voltage Us • 24 V AC/DC 0 • 110 ... 230 V AC/DC 1 3RW40 47-@@B@5 3RW40 47-@@B@5 1 2 B T