© Siemens AG 2010 SIRIUS 3RW Soft Starters 3RW30, 3RW40 for Standard Applications 3RW40 ) 4 1) Stand-alone installation. 2) Soft starter with screw terminals: delivery time class } (preferred type). 3) Soft starter with screw terminals: delivery time class A. 4) Main circuit connection: busbar connection. 5) Control by way of the internal 24 V DC supply and direct control by means of PLC possible. Note: Selection of the soft starter depends on the rated motor current. Please observe the notes for the selection of soft starters on Page 4/7. The SIRIUS 3RW40 solid-state soft starters are designed for easy starting conditions. J Load Motor .
In the event of devi- ating conditions or increased switching frequency, it may be necessary to choose a larger device. Siemens recommends the use of the selection and simulation program Win-Soft Starter. For information about rated currents for ambient temperatures > 40 °C, see "Technical specifications". * You can order this quantity or a multiple thereof. 4/18 Siemens LV 1 · 2010 3RW40 56-6BB44 3RW40 76-6BB44 Ambient temperature 40 °C Ambient temperature 50 °C Size DT Heavy starting (CLASS 20) PU (UNIT, SET, M) PS* PG Weight per PU approx.
Rated opera- tional cur- rent Ie1) Rated power of induction motors for rated opera- tional voltage Ue Rated opera- tional cur- rent Ie1) Rated power of induction motors for rated operational voltage Ue 230 V 400 V 500 V 200 V 230 V 460 V 575 V Order No. Price per PU A kW kW kW A hp hp hp hp Rated operational voltage U 200 ... 460 V2) e For DT etc. for the 3RW40 55-@BB@4 corresponding Order No.
see Selection and ordering data 3RW40 55-@BB@4 for normal starting 3RW40 56-@BB@4 • With screw or spring-type terminals 80 22 45 -- 73 20 25 50 -- S6 106 30 55 -- 98 25 30 60 -- S6 134 37 75 -- 117 30 40 75 -- S6 3RW40 55-@BB@4 3RW40 55-@BB@4 3RW40 56-@BB@4 162 45 90 -- 230 75 132 -- 280 90 160 -- 356 110 200 -- 145 40 50 100 -- S12 205 60 75 150 -- S12 248 75 100 200 -- S12 315 100 125 250 -- S12 3RW40 73-@BB@4 3RW40 74-@BB@4 3RW40 75-@BB@4 3RW40 76-@BB@4 Rated operational voltage U 400 ...
600 V3) e 3RW40 55-@BB@5 3RW40 55-@BB@5 3RW40 56-@BB@5 • With screw or spring-type terminals 80 -- 45 55 73 -- -- 50 60 S6 106 -- 55 75 98 -- -- 60 75 S6 134 -- 75 90 117 -- -- 75 100 S6 3RW40 55-@BB@5 3RW40 55-@BB@5 3RW40 56-@BB@5 162 -- 90 110 145 -- -- 100 150 S12 3RW40 73-@BB@5 230 -- 132 160 205 -- -- 150 200 S12 3RW40 74-@BB@5 280 -- 160 200 248 -- -- 200 250 S12 3RW40 75-@BB@5 356 -- 200 250 315 -- -- 250 300 S12 3RW40 76-@BB@5 Order No. supplement for connection types4) • With spring-type terminals 2 • With screw terminals 6 Order No. supplement for the rated control supply voltage Us5) • 115 V AC 3 • 230 V AC 4 3RW40 73-@BB@5 3RW40 74-@BB@5 3RW40 75-@BB@5 3RW40 76-@BB@5