© Siemens AG 2010 SIRIUS 3RW Soft Starters 3RW30, 3RW40 for Standard Applications 3RW40 More information Application examples for normal starting (Class 10) Normal starting Class 10 (up to 20 s with 350 % I n motor ), The soft starter rating can be selected to be as high as the rating of the motor used. 1) The mass inertia of the fan is Application examples for heavy starting (Class 20) 4 Heavy starting Class 20 (up to 40 s with 350 % I n motor ), The soft starter has to be selected at least one performance class higher than the motor used. Note: These tables present sample set values and device sizes. They are intended only for the purposes of information and are not binding.
The set values depend on the application in question and must be optimized during commissioning. The soft starter dimensions should be checked where necessary with the Win-Soft Starter software or with the help of Technical Assistance. 4/22 Siemens LV 1 · 2010 Application Conveyor belt Roller conveyor Compressor Small fans1) Pump Hydraulic pump 70 60 50 40 40 40 10 10 10 10 10 10 5 x IM 5 x IM 4 x IM 4 x IM 4 x IM 4 x IM 5 5 0 0 10 0 Application Stirrer Centrifuge 40 40 20 20 4 x IM 4 x IM 0 0