© Siemens AG 2010 SIRIUS 3RW Soft Starters 3RW30, 3RW40 for Standard Applications 3RW40 Configuration Status graphs The 3RW solid-state soft starters are designed for easy starting conditions. In the event of deviating conditions or increased switching frequency, it may be necessary to choose a larger de- vice. For accurate dimensioning, use the Win-Soft Starter selec- tion and simulation program. Where long starting times are involved, the integrated solid-state overload relay for heavy starting should not be disconnected. PTC sensors are recommended.
This also applies for the smooth ramp-down because during the ramp-down time an additional current loading applies in contrast to free ramp-down. In the case of high switching frequencies in S4 mode, Siemens recommends the use of PTC sensors. For corresponding device versions with integrated thermistor motor protection or separate thermistor evaluation devices see Catalog LV 1. No capacitive elements are permitted in the motor feeder be- tween the SIRIUS 3RW soft starter and the motor (e. g. no reac- tive-power compensation equipment).
In addition, neither static systems for reactive-power compensation nor dynamic PFC (Power Factor Correction) must be operated in parallel during starting and ramp-down of the soft starter. This is important to prevent faults arising on the compensation equipment and/or the soft starter. All elements of the main circuit (such as fuses and controls) should be dimensioned for direct starting, following the local short-circuit conditions. Fuses, controls and overload relays must be ordered separately. Please observe the maximum switching frequencies specified in the technical specifications.
4 Manual for SIRIUS 3RW30/40 Besides containing all important information on configuring, commissioning and servicing, the manual also contains exam- ple circuits and the technical specifications for all devices. Win-Soft Starter selection and simulation program With this software, you can simulate and select all Siemens soft starters, taking into account various parameters such as mains properties, motor and load data, and special application re- quirements. Note: When induction motors are switched on, voltage drops occur as a rule on starters of all types (direct starters, wye-delta starters, soft starters).
The infeed transformer must always be dimen- sioned such that the voltage dip when starting the motor remains within the permissible tolerance. If the infeed transformer is di- mensioned with only a small margin, it is best for the control volt- age to be supplied from a separate circuit (independently of the main voltage) in order to avoid the potential switching off of the soft starter. The software is a valuable tool, which makes complicated, lengthy manual calculations for determining the required soft starters superfluous. The Win-Soft Starter selection and simulation program can be downloaded from:
http://www.siemens.com/softstarter > Software Power electronics schematic circuit diagram More information can be found on the Internet at: http://www.siemens.com/softstarter Training course for SIRIUS soft starters (SD-SIRIUSO) L1 L2 L3 Siemens offers a 2-day training course on the SIRIUS solid-state soft starters to keep customers and own personnel up-to-date on configuring, commissioning and maintenance issues. NSB0_001485a Please direct enquiries and applications to: Training Center for Automation and Industrial Solution Gleiwitzer Strasse 555 D-90475 Nьrnberg Telephone: +49 911 895 3202 Telefax: +49 911 895 3275 E-mail:
ingeborg.hoier@siemens.com www.siemens.com/sitrain-cd T1 T2 T3 A bypass contact system and solid-state overload relay are al- ready integrated in the 3RW40 soft starter and therefore do not have to be ordered separately. 4/23 Siemens LV 1 · 2010