© Siemens AG 2010 SIRIUS 3RW Soft Starters 3RW44 Soft Starters for High-Feature Applications 3RW44 More information Application examples for normal starting (Class 10) Normal starting Class 10 (up to 20 s with 350 % I n motor ), The soft starter rating can be selected to be as high as the rating of the motor used 4 Application examples for heavy starting (Class 20) Heavy starting Class 20 (up to 40 s with 350 % I n motor ), The soft starter has to be selected one performance class higher than the motor used Application examples for very heavy starting (Class 30) Very heavy starting Class 30 (up to 60 s with 350 % I n motor ), The soft starter has to be selected two performance classes higher than the motor used 1) The mass inertia of the fan is 2) The mass inertia of the fan is 10 times the mass inertia of the motor Note:
These tables present sample set values and device sizes. They are intended only for the purposes of information and are not binding. The set values depend on the application in question and must be optimized during commissioning. The soft starter dimensions should be checked where necessary with the Win-Soft Starter software or with the help of Technical Assistance.
4/42 Siemens LV 1 · 2010 Application Conveyor belt Roller conveyor Compressor Small fans1) Pump Hydraulic pump Starting parameters • Voltage ramp and current limiting - Starting voltage % - Starting time s - Current limit value • Torque ramp - Starting torque - End torque - Starting time • Breakaway pulse 70 60 50 30 30 30 10 10 10 10 10 10 Deactivated Deactivated 4 x IM 4 x IM Deactivated Deactivated 60 50 40 20 10 10 150 150 150 150 150 150 10 10 10 10 10 10 Deactivated (0 ms) Deactivated (0 ms) Deactivated (0 ms) Deactivated (0 ms) Deactivated (0 ms) Deactivated (0 ms) Ramp-down mode Smooth ramp- down Smooth ramp- down Free ramp-down Free ramp-down Pump ramp-down Free ramp-down Application Stirrer Centrifuge Milling machine Starting parameters • Voltage ramp and current limiting - Starting voltage % - Starting time s - Current limit value • Torque ramp - Starting torque - End torque - Starting time • Breakaway pulse 30 30 30 30 30 30 4 x IM 4 x IM 4 x IM 30 30 30 150 150 150 30 30 30 Deactivated (0 ms) Deactivated (0 ms) Deactivated (0 ms) Ramp-down mode Free ramp-down Free ramp-down Free ramp-down or DC braking Application Large fans2) Mill Breakers Circular saw/bandsaw Starting parameters • Voltage ramp and current limiting - Starting voltage % - Starting time s - Current limit value • Torque ramp - Starting torque - End torque - Starting time • Breakaway pulse 30 50 50 30 60 60 60 60 4 x IM 4 x IM 4 x IM 4 x IM 20 50 50 20 150 150 150 150 60 60 60 60 Deactivated (0 ms) 80 %; 300 ms 80 %; 300 ms Deactivated (0 ms) Ramp-down mode Free ramp-down Free ramp-down Free ramp-down Free ramp-down