© Siemens AG 2010 SIRIUS 3RW Soft Starters 3RW44 Soft Starters for High-Feature Applications 3RW44 Circuit concept Configuration The SIRIUS 3RW44 soft starters can be operated in two different types of circuit. • Inline circuit The controls for isolating and protecting the motor are simply connected in series with the soft starter. The motor is con- nected to the soft starter with three cables. • Inside-delta circuit The wiring is similar to that of wye-delta starters. The phases of the soft starter are connected in series with the individual motor windings. The soft starter then only has to carry the phase cur- rent, amounting to about 58 % of the rated motor current (con- ductor current).

The 3RW44 solid-state soft starters are designed for normal starting. In case of heavy starting or increased starting fre- quency, a larger device must be selected. For long starting times it is recommended to have a PTC sensor in the motor. This also applies for the ramp-down modes smooth ramp-down, pump ramp-down and DC braking, because during the ramp-down time in these modes, an additional current load- ing applies in contrast to free ramp-down. No capacitive elements are permitted in the motor feeder be- tween the SIRIUS 3RW soft starter and the motor (e. g. no reac- tive-power compensation equipment).

In addition, neither static systems for reactive-power compensation nor dynamic PFC (Power Factor Correction) must be operated in parallel during starting and ramp-down of the soft starter. This is important to prevent faults arising on the compensation equipment and/or the soft starter. Comparison of the types of circuit All elements of the main circuit (such as fuses and controls) should be dimensioned for direct starting, following the local short-circuit conditions. Fuses, controls and overload relays must be ordered separately. 4 A bypass contact system and solid-state overload relay are al- ready integrated in the 3RW44 soft starter and therefore do not have to be ordered separately.

The harmonic component load for starting currents must be taken into consideration for the selection of motor starter protec- tors (selection of release). Note: When induction motors are switched on, voltage drops occur as a rule on starters of all types (direct starters, wye-delta starters, soft starters). The infeed transformer must always be dimen- sioned such that the voltage dip when starting the motor remains within the permissible tolerance. If the infeed transformer is di- mensioned with only a small margin, it is best for the control volt- age to be supplied from a separate circuit (independently of the main voltage) in order to avoid the potential switching off of the soft starter.

Inline circuit: Rated current I e corresponds to the rated motor current I n , 3 cables to the motor Device interface, PROFIBUS DP communication module, Soft Starter ES parameterizing and operating software The 3RW44 electronic soft starters have a PC interface for com- municating with the Soft Starter ES software or for connecting the external display and operator module. If the optional PROFIBUS communication module is used, the 3RW44 soft starter can be integrated in the PROFIBUS network and communicate using the GSD file or Soft Starter ES Premium software. Inside-delta circuit: Rated current I e corresponds to approx.

58 % of the rated motor current I n , 6 cables to the motor (as with wye-delta starters) Which circuit? Using the inline circuit involves the lowest wiring outlay. If the soft starter to motor connections are long, this circuit is preferable. With the inside-delta circuit there is double the wiring complexity but a smaller size of device can be used at the same rating. Thanks to the choice of operating mode between the inline cir- cuit and inside-delta circuit, it is always possible to select the most favorable solution. The braking function is possible only in the inline circuit. 4/43 Siemens LV 1 · 2010